with Puron® Refrigerant (R-410A)
25 to 130 Nominal Tons
Gemini® Select 38 Series outdoor condensing units feature two independent refrigerant circuits on all sizes. Each unit has its own highly efficient hermetic scroll compressor(s). All units are factory-wired and easily connected by refrigerant lines and control wiring to the matching Carrier indoor air-handling units. Various combinations of condensing units with air handlers provide packages to cover a wide range of commercial cooling solutions. Low roof-load weight distribution and weatherproof construction make these condensing units an excellent selection for rooftop or on-the-ground installations on commercial and industrial air conditioning applications.
Performance Features
- Condensing unit EERs up to 11.5 and IPLV up to 16.2
- Unit performance rated in accordance with AHRI Standard 365
- Full capacity range dual-circuit units (25-130 sizes)
- Hermetic scroll compressors with option for Digital compressor for superior part-load performance
- Novation® microchannel heat exchanger (MCHX) condenser coils with option for E-coated Novation condenser coils
- Compressor with neoprene isolators and oil heater(s)
Reliability Features
- Galvanized steel cabinet, bonderized and finished with baked enamel, 500-hour salt-spray test
- High and low-pressure protection
- Compressor overload protection
- Loss of charge and low suction superheat protection
- Self contained 24-v CCN (Carrier Comfort Network) controls including transformer
- Low ambient head pressure control
- UL, CSA, and ETL approved
Maintenance Features
- Oil-level sight glass, filter driers, liquid line solenoid valve
- Access panel accessibility to compressor and control box
- Compressor suction service valves and liquid shutoff valves
Installation Features
- Shipped with nitrogen holding charge
- On-the-ground or rooftop installation
- 24V control circuit transformer permits quick, easy wiring of thermostats
Performance Features
- Condensing unit EERs up to 11.5 and IPLV up to 16.2
- Unit performance rated in accordance with AHRI Standard 365
- Full capacity range dual-circuit units (25-130 sizes)
- Hermetic scroll compressors with option for Digital compressor for superior part-load performance
- Novation® microchannel heat exchanger (MCHX) condenser coils with option for E-coated Novation condenser coils
- Compressor with neoprene isolators and oil heater(s)
Reliability Features
- Galvanized steel cabinet, bonderized and finished with baked enamel, 500-hour salt-spray test
- High and low-pressure protection
- Compressor overload protection
- Loss of charge and low suction superheat protection
- Self contained 24-v CCN (Carrier Comfort Network) controls including transformer
- Low ambient head pressure control
- UL, CSA, and ETL approved
Maintenance Features
- Oil-level sight glass, filter driers, liquid line solenoid valve
- Access panel accessibility to compressor and control box
- Compressor suction service valves and liquid shutoff valves
Installation Features
- Shipped with nitrogen holding charge
- On-the-ground or rooftop installation
- 24V control circuit transformer permits quick, easy wiring of thermostats
38APD Capacity Ratings
Size | 60Hz | 50Hz | ||||||
---|---|---|---|---|---|---|---|---|
Capacity Nominal Tons | Capacity Nominal kW | EER | IPLV | Capacity Nominal Tons | Capacity Nominal kW | EER | IPLV | |
025 | 24.0 | 84.3 | 11.0 | 13.1 | 20.0 | 70.3 | 11.6 | 16.4 |
027 | 26.6 | 93.4 | 10.9 | 14.0 | 22.2 | 78.1 | 11.7 | 15.4 |
030 | 31.1 | 109.2 | 10.8 | 12.8 | 26.0 | 91.4 | 11.5 | 14.2 |
040 | 39.2 | 137.7 | 11.5 | 15.3 | 32.6 | 114.6 | 12.0 | 17.4 |
050 | 50.0 | 175.6 | 11.1 | 14.9 | 41.6 | 146.3 | 11.4 | 16.7 |
060 | 58.3 | 204.7 | 11.0 | 14.5 | 48.0 | 168.8 | 11.5 | 16.4 |
070 | 67.3 | 236.4 | 11.0 | 15.7 | 58.5 | 205.7 | 11.3 | 17.7 |
080 | 78.0 | 273.9 | 11.1 | 15.6 | 64.5 | 226.8 | 11.5 | 17.5 |
090 | 87.4 | 306.9 | 11.3 | 15.3 | 71.9 | 252.8 | 11.8 | 17.4 |
100 | 96.0 | 337.2 | 11.1 | 15.0 | 79.8 | 280.3 | 11.6 | 16.9 |
115 | 110.4 | 388.3 | 11.1 | 15.2 | 90.8 | 319.3 | 11.6 | 17.1 |
130 | 125.1 | 442.3 | 11.1 | 15.2 | 103.7 | 364.6 | 11.5 | 17.1 |
EER = Energy Efficiency Ratio IPLV = Integrated Part Load Value
NOTES
1. Unit performance is rated in accordance with ARI (Air Conditioning and Refrigeration Institute) Standard 365.
2. Ratings are based on 45°F (7.2°C) saturated suction temperature and 95°F (35°C) outside-air temperature, and include suction line losses
38APD (Dual Circuit) Weights and Dimensions
Size | Operating Weight (lbs) | Dimensions (in) | ||
---|---|---|---|---|
Length | Width | Height | ||
025 | 1095 | 88.24 | 40.34 | 61.0 |
027 | 1258 | 88.24 | 40.34 | 73.1 |
030 | 1264 | 88.24 | 40.34 | 73.1 |
040 | 2094 | 92.13 | 88.24 | 73.0 |
050 | 2120 | 92.13 | 88.24 | 73.0 |
060 | 2227 | 92.13 | 88.24 | 73.0 |
070 | 2450 | 110.84 | 88.24 | 73.0 |
080 | 2610 | 151.09 | 88.25 | 73.0 |
090 | 2835 | 151.09 | 88.25 | 73.0 |
100 | 2844 | 151.09 | 88.25 | 73.0 |
115 | 3211 | 191.34 | 88.25 | 73.0 |
130 | 3353 | 191.34 | 88.25 | 73.0 |