ZS Immersion Sensors ZS-IMM
ZS Immersion Sensors ZS-IMM Carrier ZS Sensor Air Conditioner Sensor Selangor, Malaysia, Kuala Lumpur (KL), Singapore, Puchong, Petaling Jaya (PJ), Pandan Jaya Supplier, Suppliers, Supply, Supplies | United Faith Sdn Bhd
The Carrier line of communicating ZS immersion sensors are designed to monitor water temperature in pipe applications. The sensor is potted inside a 1/4” stainless steel probe with a thermally conductive compound. All immersion units are mounted in a thermowell and have etched Teflon® lead-wires and double encapsulated sensors to create a watertight package that can withstand a wide range of humidity and condensation.

The ZS immersion sensors connect directly to the dedicated sensor network (Rnet) of a Carrier i-Vu controller. This communicating sensor network supports up to 15 ZS sensors through a single port, eliminating the need to consume multiple inputs on the controller.
 

Sensing Element Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.36°F (0.2°C)
Sensor Range: 20° to 120°F (-5° to 50°C)
Accuracy: ±0.9°F (0.5°C)
Enclosure Material Polycarbonate, UL94V-0
Enclosure Rating NEMA 4, IP66, UV rated
Enclosure Dimensions Width: 5 in. (12.7 cm)
Height: 4.15 in. (10.54 cm)
Depth: 2.5 in. (6.35 cm)
Probe 304 SS 0.25'' (0.64 cm) diameter 2 or 4 in. (5.08 or 10.16 cm) length specified at time of order
Power Requirements 12 Vdc @ 6 mA
Power Supply The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For additional power, use an external power supply. Use the above power requirements to calculate the size of the external power supply. The controller and the external power supply must share a common ground.
Communication 115 kbps
Environmental operating range -40 to 158°F (-40 to 70°C)
Mounting Sensor's 1/2 in. NPSM plastic threads are screwed into a thermowell
Listed by FCC Part 15-Subpart B-Class B, CE