Enthalpy Switch:Receiver 33CSENTHSW
Enthalpy Switch:Receiver 33CSENTHSW Carrier Non Communicating Sensors Air Conditioner Sensor Selangor, Malaysia, Kuala Lumpur (KL), Singapore, Puchong, Petaling Jaya (PJ), Pandan Jaya Supplier, Suppliers, Supply, Supplies | United Faith Sdn Bhd
The accessory enthalpy switch/receiver measures both temperature and humidity and converts the data into a relay output dependent on the sensor mode. Mode 1 is designed to energize the relay at a fixed set point of 28 BTU/lb or 75 F.

  • Advanced technology ceramic design enables sensors to recover fully from condensation
  • Sensor maintains accuracy longer than conventional sensors
  • Accuracy is maintained over the entire operating range by using temperature compensation
  • Precise production tolerances allow sensor interchangeability
  • Each sensor is tested to work at numerous points

Operating range of -40 to 140°F (-40 to 60°C) and 0-100% RH non condensing

Enthalpy range of 0 to 50 Btu/lb

Enthalpy accuracy of +/- 1Btu/lb at 77°F (25°C)


Please leave your enquiry here, we will reply as soon as possible.


*only support gif, jpeg, jpg, png, pdf
Switch To Desktop Version